Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
48V
120W
2.5A
3 x 340-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
123.6 x 40 x 116.8 mm
4.87” x 1.57” x 4.60”
0.60 kg (1.32 lb)
| Model | Description |
|---|---|
| DRL-48V120W3ENA | Option Type for 340-600 Vac and Conformal Coating |
48V
120W
2.5A
3 x 340-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
123.6 x 40 x 116.8 mm
4.87” x 1.57” x 4.60”
0.60 kg (1.32 lb)
| Model | Description |
|---|---|
| DRL-48V120W3ENA | Option Type for 340-600 Vac and Conformal Coating |
|
Output Current
2.5A
|
|
Output Voltage
48V
|
|
Output Voltage Range
|
|
Output Voltage Adjustment Range
48-55 Vdc
|
|
Output Power
120W
|
|
Output Current Adjustment Range
|
|
Max Output Voltage
|
|
Buffering Time
-
|
|
Line Regulation
± 0.5%
|
|
Load Regulation
± 1%
|
|
PARD
< 100 mVpp typ. @ 0°C to +70°C
< 300 mVpp typ. @ -30°C to 0°C |
|
Start-up Time
1500 ms typ. @ nominal input (100% load)
|
|
Hold-up Time
20 ms typ. @ 3 x 400 Vac (100% load)
|
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 10% @ 3 x 340-575 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle@ 5 Hz & 10 kHz)
|
|
Start-up with Capacitive Loads
3,000 µF Max
|
|
Remote ON/OFF
-
|
|
Protective Device
-
|
|
Voltage Drop Between Input and Output
-
|
|
Residual Ripple/PARD (20MHz)
-
|
|
Residual Ripple
-
|
|
Max. Power
-
|
|
Ripple & Noise
-
|
|
LED System Voltage Range in CC Mode
-
|
|
Rise Time
30 ms typ. @ nominal input (100% load)
|
|
Power Boost Duration
-
|
|
Power Boost Recovery Time
-
|
|
Peak Power
-
|
|
Nominal Input Voltage
3 x 380-500 Vac
|
|
Input Voltage Range
3 x 340-575 Vac (3-Phase) or 2 x 340-575 Vac (2-Phase)
|
|
Max Input Voltage
-
|
|
Nominal Input Frequency
50-60 Hz
|
|
Input Frequency Range
47-63Hz
|
|
Nominal DC Input Voltage
|
|
DC Input Voltage Range
-
|
|
Input Current
< 0.69 A @ 3 x 400 Vac,
< 0.6 A @ 3 x 500 Vac |
|
Input Power (Standby Mode)
-
|
|
Efficiency at 100% load
86.5% typ. @ 3 x 400 Vac & 3 x 500 Vac
|
|
Inrush Current
40 A typ. @ 3 x 400 Vac & 3 x 500 Vac
|
|
Charging Time
-
|
|
Power Factor at 100% load
> 0.4 @ 3 x 400 Vac & 3 x 500 Vac
|
|
Leakage Current
< 1 mA @ 3 x 400 Vac & 3 x 500 Vac
|
|
Nominal Current
-
|
|
Total Harmonic Distortion
-
|
|
Power Dissipation
-
|
|
Efficiency @ 10% load
-
|
|
Input Voltage Phase
-
|
|
Case Chassis / Cover
Aluminium / SGCC
|
|
|
Indicator
Green LED DC OK
|
|
|
Cooling System
Convection
|
|
|
Input Terminal
4 Pins (Rated 600 V / 30 A)
|
|
|
Output Terminal
4 Pins (Rated 600 V / 30 A)
|
|
|
Signal Terminal
-
|
|
|
Noise Sound Pressure Level (SPL)
< 25 dBA
|
|
|
Input/Output Terminal
-
|
|
|
Signal
-
|
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
|
Wire
Input: AWG 18-10
Output: AWG 18-10 |
|
|
Protection Structure
-
|
|
|
Terminal
-
|
|
|
Unit Weight
0.60 kg (1.32 lb)
|
Dimensions
123.6 x 40 x
116.8 mm
4.87” x 1.57” x 4.60” |
|
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz @ 19.6 m/s² (2 G peak); 10 min per cycle, 60 min for X, Y, Z direction.
|
|
Shock Test (Operating)
-
|
|
Operating Temperature
-40°C to +70°C
|
|
Storage Temperature
-40°C to +85°C
|
|
Power De-rating
> 50°C de-rate power by 2.5 % / °C
|
|
Operating Humidity
5 to 95% RH (Non-Condensing)
|
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, 9 times in total
|
|
Vibration (Non-Operating)
IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction
|
|
Storage Humidity
-
|
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
|
|
Pollution Degree
2
|
|
Bump Test (Operating)
-
|
|
Over Voltage Category
II (Compliance to EN 62477-1 OVC III with 2,000 meters altitude)
|
|
Corrosion
-
|
|
Acoustic Noise
-
|
|
Shock
-
|
|
Vibration
-
|
|
Overvoltage
< 68 V, SELV Output, Auto-recovery Mode
|
|
Overload / Overcurrent
105 – 165% of rated load current, Auto-recovery (150% Power Boost for 500 ms)
|
|
Over Temperature
Non-Latching (Auto-recovery)
|
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed)
|
|
Reverse Polarity Protection
-
|
|
Degree of Protection
IP20
|
|
Protection Against Shock
Class I with Primary Earth connection
|
|
Input Polarity Protection
-
|
|
Battery Polarity Protection
-
|
|
Wrong Battery Voltage Protection
-
|
|
Deep Discharge Protection
-
|
|
Overload
-
|
|
Overcurrent
-
|
|
Internal Fuse
-
|
|
Insufficient Input Voltage Protection
-
|
|
MTBF
Telcordia SR-332: > 700,000 hrs.
I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 100% load, Ta: 25°C |
|
Expected Cap Life Time
10 Years
I/P: 3 x 400 Vac & 3 x 500 Vac, O/P: 50% load, Ta: 40°C |
|
Safety Certificate
-
|
|
Electrical Safety
TUV Bauart: IEC/EN 62368-1
UL/cUL: UL 62368-1, CSA C22.2; UL 61010-1/-2-201, CAN/CSA-C22.2 No. 61010-1-12 CB scheme: IEC/EN/BS EN 62368-1, AS/NZS 62368-1; IEC/EN 61010-1/-2-201 CCC: GB4943.1 BIS: IS 13252-1 (Part 1) BSMI: CNS15598-1 EAC: TP TC 004/2011 KC: KC 62368-1 (upon request) |
|
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
|
Medical Safety
-
|
|
Galvanic Isolation
Input to Output: 4.0 kVac
Input to Ground: 2.5 kVac Output to Ground: 0.5 kVac |
|
Industrial Control Equipment
-
|
|
Hazardous Location / ATEX
-
|
|
II 3 G ATEX 2014/34/EU
-
|
|
Electrical Equipments of Machines
-
|
|
Electrical Equipment for Use in Electrical Power Installations
-
|
|
Safety Entry Low Voltage
SELV (IEC/EN 61010-1/2-201, IEC/EN 62368-1)
|
|
Maritime
-
|
|
Material and Parts
-
|
|
Isolation Resistance
-
|
|
PE Resistance
-
|
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
|
Certificates for Other Countries
-
|
|
BIS
-
|
|
KC
-
|
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
|
ITE Safety
-
|
|
SIL3
-
|
|
Emission
(CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032, AS/NZS CISPR 32, Class B; KS C 9832; CNS15936; EN/EN BS 61000-6-4, EN/BS EN 61204-3; Compliance to FCC Title 47 |
|
Immunity
Generic Standards: EN/BS EN 55035; KS C 9835; EN/BS EN 61000-6-2 ; EN/BS EN 61204-3
|
|
Harmonic Current Emissions
IEC/EN/EN BS 61000-3-2, Class A
|
|
Voltage Fluctuation and Flicker
IEC/EN/EN BS 61000-3-3, dmax ≤ 4%
|
|
ESD Immunity
-
|
|
Radiated Immunity
-
|
|
EFT
-
|
|
Surge
-
|
|
Conducted Immunity
-
|
|
Magnetic Field
-
|
|
Voltage Dips
-
|
|
Component Power Supply for General Use
-
|
48V
960W
20A
3 x 320-575 Vac
24V
960W
40A
3 x 340-575 Vac
5V
15W
3A
85-264 Vac
24V
120W
5A
3 x 340-575 Vac