24V
960W
40A
85-264Vac
124 x 125 x 133.6 mm
4.88” x 4.92” x 5.26”
2.87 kg (6.33 lb)
24V
960W
40A
85-264Vac
124 x 125 x 133.6 mm
4.88” x 4.92” x 5.26”
2.87 kg (6.33 lb)
|
Output Current
40A
|
|
Output Voltage
24V
|
|
Output Voltage Range
|
|
Output Voltage Adjustment Range
24-28Vdc
|
|
Output Power
960W
|
|
Output Current Adjustment Range
|
|
Max Output Voltage
|
|
Buffering Time
-
|
|
Line Regulation
10mV Max. (@ 85-264Vac input, 100% load)
|
|
Load Regulation
50mV Max. (@ single mode, 0-100% load)
1000mV Typ. (@ parallel mode, 0-100% load) |
|
PARD
100mVpp Max.
|
|
Start-up Time
800ms Max. @ 100Vac & 120Vac & 230Vac
|
|
Hold-up Time
24ms Typ. @ 100Vac & 120Vac & 230Vac (100% load)
|
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0.7-40A load
Slew rate 0.1A/µs (@ 5Hz, 50Hz & 1kHz, 50% Duty Cycle) |
|
Start-up with Capacitive Loads
40,000µF Max.
|
|
Remote ON/OFF
-
|
|
Protective Device
-
|
|
Voltage Drop Between Input and Output
-
|
|
Residual Ripple/PARD (20MHz)
-
|
|
Residual Ripple
-
|
|
Max. Power
-
|
|
Ripple & Noise
-
|
|
LED System Voltage Range in CC Mode
-
|
|
Rise Time
75ms Max. @ 100Vac & 120Vac & 230Vac (0µF, 24V, 40A)
75ms Max. @ 100Vac & 120Vac & 230Vac (40,000µF, 24V, 40A) |
|
Power Boost Duration
5 seconds Typ.
7 seconds Max. |
|
Power Boost Recovery Time
17 seconds Typ.
|
|
Nominal Input Voltage
100-240Vac
|
|
Input Voltage Range
85-264Vac
|
|
Max Input Voltage
-
|
|
Nominal Input Frequency
50-60Hz
|
|
Input Frequency Range
47-63Hz
|
|
Nominal DC Input Voltage
|
|
DC Input Voltage Range
-
|
|
Input Current
10.50A Typ. @ 100Vac, 8.60A Typ. @ 120Vac, 4.50A Typ. @ 230Vac
|
|
Input Power (Standby Mode)
-
|
|
Efficiency at 100% load
94.10% Typ. @ 100Vac, 94.71% Typ. @ 120Vac, 95.98% Typ. @ 230Vac
|
|
Inrush Current
11A Max. @ 100Vac, 13A Max. @ 120Vac, 20A Max. @ 230Vac
|
|
Charging Time
-
|
|
Power Factor at 100% load
0.99 Typ. @ 100Vac, 0.99 Typ. @ 120Vac, 0.96 Typ. @ 230Vac
|
|
Leakage Current
(Enclosure to Neutral)
0.50mA / 1.21mA @ 110Vac, 50Hz, TN/TT system / IT system 0.71mA / 1.73mA @ 132Vac, 50Hz, TN/TT system / IT system 1.18mA / 2.82mA @ 264Vac, 50Hz, TN/TT system / IT system |
|
Nominal Current
-
|
|
Total Harmonic Distortion
-
|
|
Power Dissipation
0% load:
5.58W Typ. @ 100Vac, 4.61W Typ. @ 120Vac, 3.70W Typ. @ 230Vac 13.9W Max. @ 100Vac, 13.1W Max. @ 120Vac, 13.2W Max. @ 230Vac 100% load: 60.32W Typ. @ 100Vac, 53.71W Typ. @ 120Vac, 40.21W Typ. @ 230Vac 70.00W Max. @ 100Vac, 65.60W Max. @ 120Vac, 54.80W Max. @ 230Vac |
|
Efficiency @ 10% load
-
|
|
Case Chassis / Cover
Aluminium
|
|
|
Indicator
Green LED (DC OK) and Red LED (Overload)
|
|
|
Cooling System
Convection
|
|
|
Input Terminal
3 Pins (Rated 600V/35A)
|
|
|
Output Terminal
4 Pins (Rated 300V/65A)
|
|
|
Signal Terminal
5 Pins (Rated 300V/10A)
|
|
|
Noise Sound Pressure Level (SPL)
< 25dBA
|
|
|
Input/Output Terminal
-
|
|
|
Signal
-
|
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
|
Wire
Input: AWG 14-8
Output: AWG: 10-6 Signal: AWG 20-16 |
|
|
Protection Structure
-
|
|
|
Terminal
-
|
|
|
Unit Weight
2.87 kg (6.33 lb)
|
Dimensions
124 x 125 x
133.6 mm
4.88” x 4.92” x 5.26” |
|
Vibration (Operating)
-
|
|
Shock Test (Operating)
-
|
|
Operating Temperature
-25°C to +70°C (Cold start -40°C)
|
|
Storage Temperature
-40°C to +85°C
|
|
Power De-rating
Vertical Mounting:
Temperature: > 60°C de-rate power by 2.5% / °C Input Voltage: If < 90Vac, > 55°C de-rate power by 1.67% / °C Horizontal Mounting: Temperature: > 40°C de-rate power by 1.67% / °C Input Voltage: If < 90Vac, > 35°C de-rate power by 1.43% / °C |
|
Operating Humidity
5 to 95% RH (Non-Condensing)
|
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 6 times in total
|
|
Vibration (Non-Operating)
IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
|
|
Storage Humidity
-
|
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
0 to 2,500 Meters (8,200 ft.) for IEC/EN 61558 |
|
Pollution Degree
2
|
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
|
Over Voltage Category
III
According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
|
Corrosion
-
|
|
Overvoltage
< 32V, SELV Output, Hiccup Mode, Non-Latching (Auto- Recovery)
|
|
Overload / Overcurrent
> 150% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
|
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
|
Reverse Polarity Protection
-
|
|
Degree of Protection
IP20
|
|
Protection Against Shock
Class I with Primary Earth connection
|
|
Input Polarity Protection
-
|
|
Battery Polarity Protection
-
|
|
Wrong Battery Voltage Protection
-
|
|
Deep Discharge Protection
-
|
|
Overload
-
|
|
Overcurrent
-
|
|
Internal Fuse
-
|
|
Insufficient Input Voltage Protection
-
|
|
MTBF
513,800 hrs. (I/P: 100Vac, O/P: 24V, 40A, Ta: 25°C)
312,900 hrs. (I/P: 100Vac, O/P: 24V, 40A, Ta: 40°C) |
|
Expected Cap Life Time
131,400 hrs. @ 100Vac & 230Vac (O/P: 24V, 40A, Ta: 25°C)
131,400 hrs. @ 100Vac & 230Vac (O/P: 24V, 20A, Ta: 25°C) 60,000 hrs. @ 100Vac (O/P: 24V, 40A, Ta: 40°C) 92,000 hrs. @ 230Vac (O/P: 24V, 40A, Ta: 40°C) 131,400 hrs. @ 100Vac (O/P: 24V, 20A, Ta: 40°C) 115,400 hrs. @ 230Vac (O/P: 24V, 20A, Ta: 40°C) |
|
Safety Certificate
-
|
|
Electrical Safety
SIQ Bauart: EN 62368-1, EN 61558-1, EN 61558-2-16, EN 61010-1, EN 61010-2-201
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1, IEC 61558-1, IEC 61558-2-16, IEC 61010-1, IEC 61010-2-201 UKCA: BS EN 62368-1, BS EN 61558-1, BS EN 61558-2-16, BS EN 61010-1, BS EN 61010-2-201 |
|
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
|
Medical Safety
-
|
|
Galvanic Isolation
Input / Output: 4.54KVac
Input / PE: 2.5KVac Input / DC OK relay contact: 4.54KVac (Recommend to connect DC OK pins together with output pins) Output / PE: 1.5KVac Output / DC OK relay contact: 0.5KVac DC OK relay contact / PE: 1.5KVac |
|
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564) |
|
Hazardous Location / ATEX
-
|
|
II 3 G ATEX 2014/34/EU
-
|
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
|
Maritime
DNV GL: Germanischer Lloyd classified
ABS: American Bureau for Shipping) PDA Environmental category: C, EMC2 |
|
Material and Parts
-
|
|
Isolation Resistance
> 5MOhm (Input to Output, 500Vdc)
|
|
PE Resistance
< 0.1Ohm
|
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
|
Certificates for Other Countries
-
|
|
BIS
-
|
|
KC
-
|
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
|
ITE Safety
-
|
|
SIL3
-
|
|
Emission
(CE & RE)
Generic Standards: EN/BS EN 61000-6-3 CISPR 32, EN/BS EN 55032, KN 32, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
|
Immunity
Generic Standards: EN/BS EN 55024, KN 35, EN/BS EN 61000-6-2
|
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
|
ESD Immunity
-
|
|
Radiated Immunity
-
|
|
EFT
-
|
|
Surge
-
|
|
Conducted Immunity
-
|
|
Magnetic Field
-
|
|
Voltage Dips
-
|
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
24V
240W
10A
85-277 Vac (305
12V
120W
10A
85-277 Vac (305
5V
15W
3A
85-264 Vac
48V
240W
5A
85-277 Vac (305
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.