Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
48V
108W
2.3A
180-264 Vac
129 x 97 x 30 mm
5.08” x 3.82” x 1.18”
0.285 kg (0.63 lb)
48V
108W
2.3A
180-264 Vac
129 x 97 x 30 mm
5.08” x 3.82” x 1.18”
0.285 kg (0.63 lb)
|
Output Current
2.3A
|
|
Output Voltage
48V
|
|
Output Voltage Range
|
|
Output Voltage Adjustment Range
43.2-52.8 Vdc
|
|
Output Power
108W
|
|
Output Current Adjustment Range
|
|
Max Output Voltage
|
|
Buffering Time
-
|
|
Line Regulation
± 0.5% (@ 230 Vac input)
|
|
Load Regulation
± 0.5% (@ 230 Vac input)
|
|
PARD
< 200 mVpp @ 0°C to 70°C
600 mVpp typ. @ -30°C to 0°C |
|
Start-up Time
500 ms typ. @ 230 Vac
|
|
Hold-up Time
42 ms typ. @ 230 Vac
|
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 10% @ 230 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle @ 5 Hz & 10 KHz)
|
|
Start-up with Capacitive Loads
2,000µF Max
|
|
Remote ON/OFF
-
|
|
Protective Device
-
|
|
Voltage Drop Between Input and Output
-
|
|
Residual Ripple/PARD (20MHz)
-
|
|
Residual Ripple
-
|
|
Max. Power
-
|
|
Ripple & Noise
-
|
|
LED System Voltage Range in CC Mode
-
|
|
Rise Time
30 ms typ. @ 230 Vac
|
|
Power Boost Duration
-
|
|
Power Boost Recovery Time
-
|
|
Nominal Input Voltage
200-240 Vac
|
|
Input Voltage Range
180-264 Vac
|
|
Max Input Voltage
-
|
|
Nominal Input Frequency
50-60 Hz
|
|
Input Frequency Range
47-63Hz
|
|
Nominal DC Input Voltage
|
|
DC Input Voltage Range
-
|
|
Input Current
1.2 A typ. @ 230 Vac
|
|
Input Power (Standby Mode)
-
|
|
Efficiency at 100% load
90.5% typ.
|
|
Inrush Current
55 A typ. @ 230 Vac
|
|
Charging Time
-
|
|
Power Factor at 100% load
-
|
|
Leakage Current
< 0.5 mA @ 240 Vac
|
|
Nominal Current
-
|
|
Total Harmonic Distortion
-
|
|
Power Dissipation
-
|
|
Efficiency @ 10% load
-
|
|
Case Chassis / Cover
SGCC / Aluminium
|
|
|
Indicator
Green LED (DC OK)
|
|
|
Cooling System
Convection
|
|
|
Input Terminal
M3.5 x 7 Pins (Rated 300 V / 20 A)
|
|
|
Output Terminal
-
|
|
|
Signal Terminal
-
|
|
|
Noise Sound Pressure Level (SPL)
< 25dBA
|
|
|
Input/Output Terminal
-
|
|
|
Signal
-
|
|
|
Mounting Rail
-
|
|
|
Wire
AWG 18-12
Current rating can refer to page 6 “Wire AWG Table” |
|
|
Protection Structure
-
|
|
|
Terminal
-
|
|
|
Unit Weight
0.285 kg (0.63 lb)
|
Dimensions
129 x 97 x
30 mm
5.08” x 3.82” x 1.18” |
|
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 20 Hz to 500 Hz (5G); 10 min per cycle, 60 min for each axis (X, Y,Z)
|
|
Shock Test (Operating)
IEC 60068-2-27, Half Sine Wave: 10G for a duration of 11 ms, 3 shock for each 3 directions
|
|
Operating Temperature
-40°C to +70°C
|
|
Storage Temperature
-40°C to +85°C
|
|
Power De-rating
> 50°C de-rate power by 2% / °C
|
|
Operating Humidity
20 to 90% RH (Non-Condensing)
|
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 50G for a duration of 11 ms, 3 shocks for each 3 directions
|
|
Vibration (Non-Operating)
IEC 60068-2-6, Random: 5 Hz to 500 Hz (2.09G); 20 min per axis for all X, Y, Z direction
|
|
Storage Humidity
-
|
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
|
|
Pollution Degree
3
|
|
Bump Test (Operating)
-
|
|
Over Voltage Category
II (Compliance to EN 62477-1 OVC III with 2000 meters altitude)
|
|
Corrosion
-
|
|
Overvoltage
52.8 V-64.8 V
SELV Output, Latch Mode |
|
Overload / Overcurrent
110-175% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery)
|
|
Over Temperature
Latch Mode
|
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
|
Reverse Polarity Protection
-
|
|
Degree of Protection
-
|
|
Protection Against Shock
Class I with Primary Earth connection
|
|
Input Polarity Protection
-
|
|
Battery Polarity Protection
-
|
|
Wrong Battery Voltage Protection
-
|
|
Deep Discharge Protection
-
|
|
Overload
-
|
|
Overcurrent
-
|
|
Internal Fuse
-
|
|
Insufficient Input Voltage Protection
-
|
|
MTBF
> 700,000 hrs as per Telcordia SR-332 (I/P: 230Vac, O/P: 100% Load, Ta: 25°C)
|
|
Expected Cap Life Time
10 years (230Vac, 50% load @ 40°C)
|
|
Safety Certificate
-
|
|
Electrical Safety
CB scheme: IEC 62368-1
CCC: GB 4943.1 BIS: IS 13252 (Part 1) |
|
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
|
Medical Safety
-
|
|
Galvanic Isolation
Input to Output: 4.0 KVac
Input to Ground: 2.0 KVac Output to Ground: 1.25 KVac |
|
Industrial Control Equipment
-
|
|
Hazardous Location / ATEX
-
|
|
II 3 G ATEX 2014/34/EU
-
|
|
Electrical Equipments of Machines
-
|
|
Electrical Equipment for Use in Electrical Power Installations
-
|
|
Safety Entry Low Voltage
-
|
|
Maritime
-
|
|
Material and Parts
-
|
|
Isolation Resistance
-
|
|
PE Resistance
-
|
|
UKCA
-
|
|
Certificates for Other Countries
-
|
|
BIS
-
|
|
KC
-
|
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
|
ITE Safety
-
|
|
SIL3
-
|
24V
108W
4.5A
90-264Vac
36V
108W
3A
90-264Vac
48V
110W
2.3A
90-264Vac
24V
108W
4.5A
180-264 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.