24V
480W
20A
85-276Vac
124 x 82 x 149 mm
4.88” x 3.23” x 5.87”
1.45 kg (3.20 lb)
24V
480W
20A
85-276Vac
124 x 82 x 149 mm
4.88” x 3.23” x 5.87”
1.45 kg (3.20 lb)
|
Output Current
20A
|
|
Output Voltage
24V
|
|
Output Voltage Range
|
|
Output Voltage Adjustment Range
24-28Vdc
|
|
Output Power
480W
|
|
Output Current Adjustment Range
|
|
Max Output Voltage
|
|
Buffering Time
-
|
|
Line Regulation
10mV Max. (@ 85-276Vac input, 100% load)
|
|
Load Regulation
100mV Max. (@ 85-276Vac input, 0-100% load)
|
|
PARD
100mVpp Max.
|
|
Start-up Time
1000ms Max. @ 100Vac & 120Vac & 230Vac
|
|
Hold-up Time
43ms Typ. @ 100Vac & 120Vac & 230Vac (100% load)
|
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
Slew rate 0.1A/µs (@ 5Hz, 50Hz & 1kHz, 50% Duty Cycle) |
|
Start-up with Capacitive Loads
20,000µF Max.
|
|
Remote ON/OFF
-
|
|
Protective Device
-
|
|
Voltage Drop Between Input and Output
-
|
|
Residual Ripple/PARD (20MHz)
-
|
|
Residual Ripple
-
|
|
Max. Power
-
|
|
Ripple & Noise
-
|
|
LED System Voltage Range in CC Mode
-
|
|
Rise Time
100ms Max. @ 100Vac & 120Vac & 230Vac (0µF, 24V, 20A)
100ms Max. @ 100Vac & 120Vac & 230Vac (20,000µF, 24V, 20A) |
|
Power Boost Duration
5 seconds Typ.
7 seconds Max. |
|
Power Boost Recovery Time
17 seconds Typ.
|
|
Nominal Input Voltage
100-240Vac
|
|
Input Voltage Range
85-276Vac
|
|
Max Input Voltage
-
|
|
Nominal Input Frequency
50-60Hz
|
|
Input Frequency Range
47-63Hz
|
|
Nominal DC Input Voltage
110-300Vdc
|
|
DC Input Voltage Range
Vertical Mounting: 88-375Vdc
Horizontal Mounting: 100-375Vdc |
|
Input Current
5.11A Typ. @ 100Vac, 4.24A Typ. @ 120Vac, 2.29A Typ. @ 230Vac
|
|
Input Power (Standby Mode)
-
|
|
Efficiency at 100% load
93.37% Typ. @ 100Vac, 93.83% Typ. @ 120Vac, 94.17% Typ. @ 230Vac
|
|
Inrush Current
13A Max. @ 100Vac & 120Vac & 230Vac
|
|
Charging Time
-
|
|
Power Factor at 100% load
0.99 Typ. @ 100Vac, 0.99 Typ. @ 120Vac, 0.95 Typ. @ 230Vac
|
|
Leakage Current
(Enclosure to Neutral)
< 0.31mA / 0.77mA @ 110Vac, 50Hz, TN/TT system / IT system < 0.45mA / 1.13mA @ 132Vac, 50Hz, TN/TT system / IT system < 0.80mA / 2.00mA @ 264Vac, 50Hz, TN/TT system / IT system |
|
Nominal Current
-
|
|
Total Harmonic Distortion
-
|
|
Power Dissipation
0% load:
5.29W Typ. @ 100Vac, 4.75W Typ. @ 120Vac, 2.84W Typ. @ 230Vac 9.20W Max. @ 100Vac, 9.40W Max. @ 120Vac, 10.20W Max. @ 230Vac 100% load: 34.08W Typ. @ 100Vac, 31.58W Typ. @ 120Vac, 29.70W Typ. @ 230Vac 46.00W Max. @ 100Vac, 40.60W Max. @ 120Vac, 34.00W Max. @ 230Vac |
|
Efficiency @ 10% load
-
|
|
Case Chassis / Cover
Aluminium and Plastic / Aluminium
|
|
|
Indicator
Green LED (DC OK) and Red LED (Overload)
|
|
|
Cooling System
Convection
|
|
|
Input Terminal
3 Pins (Rated 600V/35A)
|
|
|
Output Terminal
6 Pins (Rated 600V/35A)
|
|
|
Signal Terminal
2 Pins (Rated 300V/10A)
|
|
|
Noise Sound Pressure Level (SPL)
< 25dBA
|
|
|
Input/Output Terminal
-
|
|
|
Signal
-
|
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
|
Wire
Input: AWG 18-8
Output: AWG: 14-12 (Ensure that all output terminals are connected) Signal: AWG 20-16 |
|
|
Protection Structure
-
|
|
|
Terminal
-
|
|
|
Unit Weight
1.45 kg (3.20 lb)
|
Dimensions
124 x 82 x
149 mm
4.88” x 3.23” x 5.87” |
|
Vibration (Operating)
-
|
|
Shock Test (Operating)
-
|
|
Operating Temperature
-25°C to +70°C
|
|
Storage Temperature
-40°C to +85°C
|
|
Power De-rating
Vertical Mounting: > 60°C de-rate power by 2.5% / °C
Horizontal Mounting: > 40°C de-rate power by 2.5% / °C |
|
Operating Humidity
5 to 95% RH (Non-Condensing)
|
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 6 times in total
|
|
Vibration (Non-Operating)
IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
|
|
Storage Humidity
-
|
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
|
|
Pollution Degree
2
|
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
|
Over Voltage Category
III
According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
|
Corrosion
-
|
|
Overvoltage
28.8 – 35.2V, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
|
|
Overload / Overcurrent
> 150% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
|
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
|
Reverse Polarity Protection
-
|
|
Degree of Protection
IP20
|
|
Protection Against Shock
Class I with Primary Earth connection
|
|
Input Polarity Protection
-
|
|
Battery Polarity Protection
-
|
|
Wrong Battery Voltage Protection
-
|
|
Deep Discharge Protection
-
|
|
Overload
-
|
|
Overcurrent
-
|
|
Internal Fuse
-
|
|
Insufficient Input Voltage Protection
-
|
|
MTBF
751,000 hrs. (I/P: 100Vac, O/P: 24V, 20A, Ta: 25°C)
424,800 hrs. (I/P: 100Vac, O/P: 24V, 20A, Ta: 40°C) |
|
Expected Cap Life Time
131,400 hrs. @ 100Vac & 230Vac (O/P: 24V, 20A, Ta: 25°C)
96,500 hrs. @ 100Vac (O/P: 24V, 20A, Ta: 40°C) 114,100 hrs. @ 230Vac (O/P: 24V, 20A, Ta: 40°C) 131,400 hrs. @ 100Vac & 230Vac (O/P: 24V, 10A, Ta: 40°C) |
|
Safety Certificate
-
|
|
Electrical Safety
SIQ Bauart: EN 62368-1, EN 61010-1, EN 61010-2-201
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1, IEC 61010-1, IEC 61010-2-201 UKCA: IEC 62368-1, IEC 61010-1, IEC 61010-2-201 |
|
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
|
Medical Safety
-
|
|
Galvanic Isolation
Input / Output: 3.0 KVac
Input / PE: 2.0 KVac Input / DC OK relay contact: 3.0 KVac (Recommend to connect DC OK pins together with output pins) Output / PE: 1.5 KVac Output / DC OK relay contact: 0.5 KVac DC OK relay contact / PE: 1.5 KVac |
|
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
|
|
Hazardous Location / ATEX
-
|
|
II 3 G ATEX 2014/34/EU
-
|
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
|
Maritime
-
|
|
Material and Parts
-
|
|
Isolation Resistance
> 5 MOhm (Input to Output, 500 Vdc)
|
|
PE Resistance
< 0.1 Ohm
|
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
|
Certificates for Other Countries
-
|
|
BIS
-
|
|
KC
-
|
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
|
ITE Safety
-
|
|
SIL3
-
|
|
Emission
(CE & RE)
Generic Standards: EN/BS EN 61000-6-3 CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
|
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
|
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
|
ESD Immunity
-
|
|
Radiated Immunity
-
|
|
EFT
-
|
|
Surge
-
|
|
Conducted Immunity
-
|
|
Magnetic Field
-
|
|
Voltage Dips
-
|
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
24V
480W
20A
85-277 Vac (305
24V
960W
40A
85-277 Vac
48V
480W
10A
3 x 320-575 Vac
48V
960W
20A
85-277 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.