Industrial Power
Click the link below to download the file.
Get your files as below link
Dowload link
12V
240W
20A
85-277 Vac (305 Vac available for 60 seconds)
124.2 x 40 x 117.1 mm
4.89” x 1.57” x 4.61”
0.67 kg (1.48 lb)
12V
240W
20A
85-277 Vac (305 Vac available for 60 seconds)
124.2 x 40 x 117.1 mm
4.89” x 1.57” x 4.61”
0.67 kg (1.48 lb)
|
Output Current
20A
|
|
Output Voltage
12V
|
|
Output Voltage Range
|
|
Output Voltage Adjustment Range
12-15 Vdc
|
|
Output Power
240W
|
|
Output Current Adjustment Range
|
|
Max Output Voltage
|
|
Buffering Time
-
|
|
Line Regulation
± 0.5% @ 230 Vac
|
|
Load Regulation
± 1.0%
|
|
PARD
< 100 mVpp @ 0°C to +70°C
< 300 mVpp @ -30°C to 0°C |
|
Start-up Time
500 ms typ. @ 230 Vac
|
|
Hold-up Time
30 ms typ. @ 115 Vac & 230 Vac (100% load)
|
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 10% @ 115 Vac & 230 Vac input, 10-100% load (Slew Rate: 2.5 A/μS, 50% duty cycle @ 5 Hz & 10 kHz)
|
|
Start-up with Capacitive Loads
10,000 µF Max
|
|
Remote ON/OFF
-
|
|
Protective Device
-
|
|
Voltage Drop Between Input and Output
-
|
|
Residual Ripple/PARD (20MHz)
-
|
|
Residual Ripple
-
|
|
Max. Power
-
|
|
Ripple & Noise
-
|
|
LED System Voltage Range in CC Mode
-
|
|
Rise Time
30 ms typ. @ 115 Vac & 230 Vac
|
|
Power Boost Duration
150% Power Boost for 5 seconds / 200% for 50ms / 500% for 5ms
|
|
Power Boost Recovery Time
-
|
|
Peak Power
-
|
|
Nominal Input Voltage
100-240 Vac
|
|
Input Voltage Range
85-277 Vac (305 Vac available for 60 seconds)
|
|
Max Input Voltage
-
|
|
Nominal Input Frequency
50-60 Hz
|
|
Input Frequency Range
47-63Hz
|
|
Nominal DC Input Voltage
|
|
DC Input Voltage Range
100-400 Vdc
|
|
Input Current
2.4 A typ. @ 115 Vac, 1.2 A typ. @ 230 Vac
|
|
Input Power (Standby Mode)
-
|
|
Efficiency at 100% load
93% typ. @ 230 Vac
|
|
Inrush Current
40 A typ. @ 230 Vac
|
|
Charging Time
-
|
|
Power Factor at 100% load
> 0.98 @ 115 Vac & > 0.95 @ 230 Vac
|
|
Leakage Current
< 0.5 mA @ 230 Vac
|
|
Nominal Current
-
|
|
Total Harmonic Distortion
-
|
|
Power Dissipation
-
|
|
Efficiency @ 10% load
-
|
|
Input Voltage Phase
-
|
|
Average Efficiency
-
|
|
No Load Power Consumption
1.1 W typ. @ 230 Vac
|
|
Case Chassis / Cover
Galvanized steel with organic coating / Aluminum alloy with organic coating
|
|
|
Indicator
Green LED DC OK
|
|
|
Cooling System
Convection
|
|
|
Input Terminal
3 Pins (Rated 600 V / 30 A)
|
|
|
Output Terminal
4 Pins (Rated 600 V / 30 A)
|
|
|
Signal Terminal
4 Pins (Rated 300 V / 7 A)
|
|
|
Noise Sound Pressure Level (SPL)
Standard TS35 DIN Rail in accordance with EN 60715
|
|
|
Input/Output Terminal
-
|
|
|
Signal
-
|
|
|
Mounting Rail
-
|
|
|
Wire
Input: AWG 18-10
Output: AWG 12-10 DC OK & Remote: AWG 22-18 |
|
|
Protection Structure
-
|
|
|
Terminal
-
|
|
|
Unit Weight
0.67 kg (1.48 lb)
|
Dimensions
124.2 x 40 x
117.1 mm
4.89” x 1.57” x 4.61” |
|
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10 Hz to 500 Hz (2G peak); 10 min per cycle, 60 min for X, Y, Z direction
|
|
Shock Test (Operating)
-
|
|
Operating Temperature
-40°C to +80°C
|
|
Storage Temperature
-40°C to +85°C
|
|
Power De-rating
Temperature:
> 60°C de-rate power by 2.5 % / °C, > 80°C de-rate power by 3.5% / °C Input Voltage: < 100 Vac de-rate power by 1% / Vac < 200 Vdc de-rate power by 0.3% / Vdc |
|
Operating Humidity
5 to 90% RH (Non-Condensing)
|
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 50 G for duration of 11 ms; 3 times per direction, 9 times in total
|
|
Vibration (Non-Operating)
IEC 60068-2-64, Random: 5 Hz to 500 Hz (2.09 G); 20 min per axis for all X, Y, Z direction
|
|
Storage Humidity
-
|
|
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
|
|
Pollution Degree
2
|
|
Bump Test (Operating)
-
|
|
Over Voltage Category
II (Compliance to EN 61558-1 OVC III with 2000 meters altitude)
|
|
Corrosion
-
|
|
Acoustic Noise
-
|
|
Shock
-
|
|
Vibration
-
|
|
Overvoltage
<19 V, SELV Output, Hiccup Mode, Auto-recovery
|
|
Overload / Overcurrent
125 - 205% of rated load current, Hiccup Mode, Auto-recovery (150% Power Boost for 5 seconds / 200% for 50ms / 500% for 5ms)
|
|
Over Temperature
Shut down, Auto-recovery
|
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
|
Reverse Polarity Protection
-
|
|
Degree of Protection
-
|
|
Protection Against Shock
Class I with Primary Earth connection
|
|
Input Polarity Protection
-
|
|
Battery Polarity Protection
-
|
|
Wrong Battery Voltage Protection
-
|
|
Deep Discharge Protection
-
|
|
Overload
-
|
|
Overcurrent
-
|
|
Internal Fuse
-
|
|
Insufficient Input Voltage Protection
-
|
|
Pollution Degree
-
|
|
MTBF
Telcordia SR-332: > 700,000 hrs.
I/P: 115 Vac & 230 Vac, O/P: 100% load, Ta: 25°C |
|
Expected Cap Life Time
10 years (115 Vac & 230 Vac, 50% load @ 50°C)
|
|
Case Temperature Rise
-
|
|
Safety Certificate
CB scheme: IEC/EN/BS EN 62368-1, AS/NZS 62368-1 RCM, IEC/EN 61010-1/2-201, IEC 61558-1/2-16, AS/NZS 61558-1/2-16 RCM
TUV Bauart: EN 62368-1 UL/cUL: UL 62368-1, CSA C22.2; UL 61010-1/-2-201, CAN/CSA-C22.2 No. 61010-1-12 CCC: GB4943.1 BIS: IS 13252-1 (Part 1) BSMI: CNS 15598-1 EAC: TP TC 004/2011 KC: KC 62368-1 (upon request) |
|
Electrical Safety
-
|
|
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
|
Medical Safety
-
|
|
Galvanic Isolation
Input to Output: 4.0 kVac
Input to Ground: 2.5 kVac Output to Ground: 1.5 kVac Output to DC OK: 500 Vac |
|
Industrial Control Equipment
-
|
|
Hazardous Location / ATEX
-
|
|
II 3 G ATEX 2014/34/EU
-
|
|
Electrical Equipments of Machines
-
|
|
Electrical Equipment for Use in Electrical Power Installations
-
|
|
Safety Entry Low Voltage
SELV (IEC/EN 62368-1 /61010-2-201 /61558-2-16)
|
|
Maritime
-
|
|
Material and Parts
-
|
|
Isolation Resistance
-
|
|
PE Resistance
-
|
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
|
Certificates for Other Countries
-
|
|
BIS
-
|
|
KC
-
|
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
|
ITE Safety
-
|
|
SIL3
-
|
|
CE/UKCA
-
|
|
Emission
(CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032, AS/NZS CISPR 32, Class B; KS C 9832; CNS15936; EN/BS EN 61204-3; Compliance to FCC Title 47 |
|
Immunity
Generic Standards: EN/BS EN 55035; KS C 9835; EN/BS EN 61204-3
|
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3, dmax ≤ 4%
|
|
ESD Immunity
-
|
|
Radiated Immunity
-
|
|
EFT
-
|
|
Surge
-
|
|
Conducted Immunity
-
|
|
Magnetic Field
-
|
|
Voltage Dips
-
|
|
Component Power Supply for General Use
-
|
48V
960W
20A
85-277 Vac (305
48V
960W
20A
3 x 320-575 Vac
12V
120W
10A
85-277 Vac (305
12V
15W
1.25A
85-264 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.